6 MDS iNET ENI Supplement MDS 05-4131A01, Rev. A
2.2 DF1/EIP PROTOCOL
CONFIGURATION
NOTE: The Rockwell application will not identify the iNET/ENI radio
properly unless the EDS file has been integrated the applica-
tion using RSlinx software. If this has not already been done,
refer to EDS FILE INTEGRATION on Page 21 for more infor-
mation.
Perform the following procedure to configure the DF1/EIP IP protocol
settings:
1. Press A if you want to change Security Descriptor Mask 1 from its
default of 0.0.0.0. In Figure 2-2, Security Descriptor Mask 1 was
changed to 192.158.16.255.
Press B if you want to change Security Descriptor Mask 2.
2. Press N to continue.
Use the Security Descriptor Mask to control which IP addresses can
access the serial device connected to the iNET/ENI. Values of 0 and
255 are considered “open,” meaning any value in that position of the
IP address is accepted. For example, the default value of 0.0.0.0 (or a
value of 255.255.255.255) would allow any IP address to access the
device. In Figure 2-2, only IP addresses beginning with 192.158.16
can access the device.
NOTE: The IP addresses shown in this manual are for example only.
See your network administrator to determine the actual values
you should use.